User Manual
EDI-120
Control Retrofit for
Electronics Diversified Inc. (EDI)
Mark VII Dimmer Racks
JOHNSON SYSTEMS INC.
www.johnsonsystems.com
Vista de página 0
1 2 3 4 5 6 ... 35 36

Resumo do Conteúdo

Página 1 - User Manual

User ManualEDI-120Control Retrofit forElectronics Diversified Inc. (EDI)Mark VII Dimmer RacksJOHNSON SYSTEMS INC.www.johnsonsystems.com

Página 2 - For Technical Assistance

www.johnsonsystems.com10OEM P3, P4, P5 and P6 Dimmer (PWM) Control Cable PinoutP3 Connector P4 Connector P5 Connector P6 ConnectorPIN FUNCTION PIN FUN

Página 3 - Introduction

www.johnsonsystems.com 11INPUT/OUTPUTCONTACTS0-10VDCANALOG INPUTS+12 VDCPOWER SUPPLY2 AMPS MAXIMUMCOMMONOVERTEMP INPUT (N.O)FIRE ALARM (N.O)SECURITY A

Página 4 - Dimensional Drawings

www.johnsonsystems.com12+12VCommon+12VAnalogInput1 Thru 4Common+12VAnalogInput1 Thru 4MaintainedNormallyOpenSwitchContactNormallyOpenThermostatSwitchO

Página 5 - Installation

www.johnsonsystems.com 13EEPROMMemory ModuleEEPROM Memory ModuleAll EDI-120 retrot control systems come equipped with a removable EEPROM memory modul

Página 6

www.johnsonsystems.com14ProgrammingSwitchesLCD DisplayInfrared LEDSystem Status LED IndicatorsUser InterfaceEDI-120 retrot control systems are equipp

Página 7

www.johnsonsystems.com 15System Status • LED IndicatorsRUN (Green)Illuminates when the power is on and the microcontroller status is in normal run mod

Página 8 - Ensure chassis is

www.johnsonsystems.com16INF HOLDDisplayed when DMX is disconnected and the systems predetermined DMX status hold (SH) time is set for innite (INF) ho

Página 9

www.johnsonsystems.com 17Quick Programming Reference to System Configuration Menu Items1. SCENESET Enable and setup 12 different backup scenes.2. FADE

Página 10 - OEM Connector Pinouts

www.johnsonsystems.com18Detailed Programming of System Configuration Menu ItemsNOTE: The programming switches can be locked out to prevent inadvertent

Página 11

www.johnsonsystems.com 192. FADETIME Set the fade time for each of the 12 scenes from 0 to 99 seconds. The factory default is 5 seconds for all 12

Página 12

www.johnsonsystems.com2WarrantyThe EDI-120 retrot control system comes with a standard one (1) year limited warranty against defects in parts and wor

Página 13 - EEPROM Memory Module

www.johnsonsystems.com206. ADDRESS Set the DMX start address. The DMX start address can be assigned from 001 to 512 and is common

Página 14 - Programming Switches

www.johnsonsystems.com 218. 2 RM SET Set the two room assignment for each of the dimmer outputs. This menu is used to assign each of the 120 dim

Página 15 - System Status • LCD Display

www.johnsonsystems.com22 Press EXECUTE to enter the menu and congure the DMX mode. DISABLED This menu is disabled to help prevent inadvertent ch

Página 16

www.johnsonsystems.com 23 DIM#:001 Press EXECUTE to select the rst dimmer number (DIM#) in the block. DIM#:120 Press MENU ( ) to edit the di

Página 17

www.johnsonsystems.com2416. DIM CURV Congure the dimmer curve for each output. There are four different dimmer curve proles that can be assigne

Página 18

www.johnsonsystems.com 2520. ANA PAT Patch the analog inputs to any combination of control channels. Press EXECUTE to enter the menu and activate

Página 19

www.johnsonsystems.com2625. TEST INC Set the test increment units to percent or hexadecimal. The levels for the dimmer test (DIM TEST) and analog

Página 20

www.johnsonsystems.com 2729. S-ALARM Select the level and control channels triggered by the security alarm input. When a contact is sensed on the

Página 21

www.johnsonsystems.com28 C 120 ØB Press EXECUTE to toggle the patch to Phase B (ØB). C 120 ØC Press EXECUTE to toggle the patch to Phase C (ØC).

Página 22

www.johnsonsystems.com 29 K:XXXXXX Shows the unique six-character hard-key code (XXXXXX). K:XXXXXX Follow the procedure below to enter the menu an

Página 23

www.johnsonsystems.com 3IntroductionThe EDI-120 is a next generation retrot electronics package designed specically for upgrading the EDI Mark VII p

Página 24

www.johnsonsystems.com30 MEMCHECK Automatically checks the EEPROM memory module for rmware type. CRC-TEST Automatically does a CRC test on the r

Página 25

www.johnsonsystems.com 3143. BACKUP Backup parameters and save them in the EEPROM memory module. All of the conguration setting parameters can be

Página 26

www.johnsonsystems.com3245. DEFAULTS Set various system conguration settings to the factory default. Press EXECUTE to enter the menu. Press

Página 27

www.johnsonsystems.com 33JSI Serial Number: ___________________Silicone Serial Number: _______________Hard-Key Code: _____________________JSI Seria

Página 28

www.johnsonsystems.com34Troubleshooting ReferenceThis manual is accurate at time of printing and subjectto revisions and technical updates as required

Página 29

www.johnsonsystems.com 35Troubleshooting ReferenceThis manual is accurate at time of printing and subjectto revisions and technical updates as require

Página 30

www.johnsonsystems.comUser ManualEDI-120 SeriesControl Retrot for Electronics Diversied Inc. (EDI)Mark VII Dimmer RacksRev. 2

Página 31

www.johnsonsystems.com4NOTE: All measurements are in inches.Packaging & ContentsEach EDI-120 retrot control system is shipped in a custom designe

Página 32

www.johnsonsystems.com 5Installation• Disconnect (turn off) the power supply to the EDI Mark VII dimmer rack(s).WARNING! Verify all power is disconnec

Página 33

www.johnsonsystems.com6• Disconnect the P1 power connector/cable. Carefully squeeze the latches on each side of the connector together to release the

Página 34 - Troubleshooting Reference

www.johnsonsystems.com 7 If more than four (4) analog inputs are required, additional equipment may be necessary to facilitate them. Consult the fact

Página 35

www.johnsonsystems.com8Ensure chassis is connected to earth ground.POWER SUPPLY INPUT120/208VAC, 3P4W, 1.3A, 60Hz120/240VAC, 1P3W, 1.3A, 60HzEXTERNAL

Página 36 - Mark VII Dimmer Racks

www.johnsonsystems.com 9Turn on and test the new EDI-120 Retrofit System• Connect (turn on) the power supply to the EDI Mark VII dimmer rack.• Verify